Instructions

ChannelAccessRead

The ChannelAccessRead instruction tries to read an EPICS ChannelAccess process variable on the network and writes its value to a workspace variable if successful. When the process variable cannot be found on the network, or copying the value to a workspace variable fails, e.g. due to incompatible types, the instruction will return FAILURE.

Attribute name

Attribute type

Mandatory

Description

channel

StringType

yes

name of the EPICS ChannelAccess channel of the process variable

outputVar

StringType

yes

name of the workspace variable (or field thereof) where to write the read value

timeout

Float64Type

no

timeout in seconds to wait for a successful channel connection (default: 2.0)

Example

This procedure will try to connect to an EPICS ChannelAccess process variable with a maximum timeout of 5 seconds. Then it will read its value and copy it to the local workspace variable. If successful, the local variable with name to-write will contain the value of the ChannelAccess process variable. Only on successful completion of the reading and write operation will the instruction return SUCCESS. In all other cases, the instruction returns FAILURE.

<ChannelAccessRead channel="seq::test::variable" timeout="5.0" outputVar="to-write"/>
<Workspace>
    <Local name="to-write"/>
</Workspace>

ChannelAccessWrite

The ChannelAccessWrite instruction tries to write a value to an EPICS ChannelAccess process variable on the network. The value is either fetched from a workspace variable or is encoded in JSON format as two attributes (type and value). When the value cannot be fetched or parsed, the process variable cannot be found on the network, or writing the value to the process variable fails, e.g. due to incompatible types, the instruction will return FAILURE.

Attribute name

Attribute type

Mandatory

Description

channel

StringType

yes

name of the EPICS ChannelAccess channel of the process variable

varName

StringType

no

name of the workspace variable (or field thereof) from where to read the value

type

StringType

no

JSON representation of the type of the value to write

value

StringType

no

JSON representation of the value to write

timeout

Float64Type

no

timeout in seconds to wait for a successful channel connection (default: 2.0)

Note

The user must provide either the varName attribute or both the type and value attributes.

Example

This procedure will try to write the floating point value 3.14 to an EPICS ChannelAccess process variable with a maximum timeout of 5 seconds. On successful completion of the operation, the instruction will return SUCCESS.

<ChannelAccessWrite channel="seq::test::variable" timeout="5.0"
                    type='{"type":"float64"}' value='3.14'/>

PvAccessRead

The PvAccessRead instruction tries to read an EPICS PvAccess process variable on the network and writes its value to a workspace variable if successful. When the process variable cannot be found on the network, or copying the value to a workspace variable fails, e.g. due to incompatible types, the instruction will return FAILURE.

Attribute name

Attribute type

Mandatory

Description

channel

StringType

yes

name of the EPICS PvAccess channel of the process variable

outputVar

StringType

yes

name of the workspace variable (or field thereof) where to write the read value

timeout

Float64Type

no

timeout in seconds to wait for a successful channel connection (default: 2.0)

Example

This procedure will try to connect to an EPICS PvAccess process variable with a maximum timeout of 5 seconds. Then it will read its value and copy it to the local workspace variable. If successful, the local variable with name to-write will contain the value of the PvAccess process variable. Only on successful completion of the reading and write operation will the instruction return SUCCESS. In all other cases, the instruction returns FAILURE.

<PvAccessRead channel="seq::test::variable" timeout="5.0" outputVar="to-write"/>
<Workspace>
    <Local name="to-write"/>
</Workspace>

PvAccessWrite

The PvAccessWrite instruction tries to write a value to an EPICS PvAccess process variable on the network. The value is either fetched from a workspace variable or is encoded in JSON format as two attributes (type and value). When the value cannot be fetched or parsed, the process variable cannot be found on the network, or writing the value to the process variable fails, e.g. due to incompatible types, the instruction will return FAILURE.

Attribute name

Attribute type

Mandatory

Description

channel

StringType

yes

name of the EPICS PvAccess channel of the process variable

varName

StringType

no

name of the workspace variable (or field thereof) from where to read the value

type

StringType

no

JSON representation of the type of the value to write

value

StringType

no

JSON representation of the value to write

timeout

Float64Type

no

timeout in seconds to wait for a successful channel connection (default: 2.0)

Note

The user must provide either the varName attribute or both the type and value attributes.

Example

This procedure will try to write the struct with floating point member value 3.14 to an EPICS PvAccess process variable with a maximum timeout of 5 seconds. On successful completion of the operation, the instruction will return SUCCESS.

<PvAccessWrite channel="seq::test::variable" timeout="5.0"
               type='{"type":"myFloat","attributes":[{"value":{"type":"float32"}}]}'
               value='{"value":3.14}'/>

RPCClient

The RPCClient executes a Remote Procedure Call on an EPICS PvAccess RPC server. As input, it uses either a literal value, encoded in JSON format as two attributes (type and value) or the value of a workspace variable. The reply from the RPC server is optionally put into a workspace variable.

Attribute name

Attribute type

Mandatory

Description

service

StringType

yes

name of EPICS PvAccess RPC server

requestVar

StringType

no

name of the workspace variable (or field thereof) from where to read the input value

type

StringType

no

JSON representation of the type of the input value

value

StringType

no

JSON representation of the input value

outputVar

StringType

no

name of the workspace variable (or field thereof) where to write the reply value

timeout

Float64Type

no

timeout in seconds to wait for a successful connection (default: 5.0)

Note

The user must provide either the requestVar attribute or both the type and value attributes.

Example

This procedure will try to execute an Remote Procedure Call on the service with name rpc@service. As an input to the RPC call it will use the structure with a zero field, encoded in the two attributes type and value. The reply of the RPC call, if successful, is written to a workspace variable. The instruction will return SUCCESS when all steps in this operation were successful.

<RPCClient service="rpc@service"
           type='{"type":"rpcStruct","attributes":[{"value":{"type":"uint64"}}]}'
           value='{"value":0}' reply="reply" timeout="3.0"/>
<Workspace>
    <Local name="reply"/>